A4BQ - Class L - Time-Delay
Amp-Trap 2000 A4BQ fuses are 20 percent more current limiting than any other Class L fuse on the market. When correctly coordinated, they bring a superior level of protection to service entrance equipment. Downstream circuit components have maximum protection against short circuit let-thru current. A4BQ's built-in 4-second time-delay characteristic (at 500percent of rated current) accommodates harmless inrush currents with no nuisance opening.
Amp-Trap 2000 A4BQ fuses are 20 percent more current limiting than any other Class L fuse on the market. When correctly coordinated, they bring a superior level of protection to service entrance equipment. Downstream circuit components have maximum protection against short circuit let-thru current. A4BQ's built-in 4-second time-delay characteristic (at 500percent of rated current) accommodates harmless inrush currents with no nuisance opening.
Product data sheets
- DS-A4BQ-Class-L-Time-Delay-Mersenpdf - 110.45 KB 
Compliance
- COM-CE-ROHS-Declaration_Class_Type_L-20-0002pdf - 161.38 KB 
Key features & benefits
- Fastest operation under short circuit conditions: Let-thru currents are typically 20 percent lower, with a corresponding let-thru energy (clearing I2t) up to 40% lower than the next fastest Class L fuse 
- Time-delay for high inrush loads such as motors and transformers, without nuisance opening 
- 300kA interrupting rating - self-certified, UL witnessed tests 
- Most current-limiting for lowest peak let-thru current; even at fault currents up to 300kA 
- Recommended for Arc Flash energy reduction 
- Pure silver links ensure lowest let-thru current and longer fuse life 
- Easy 2-to-1 selectivity for prevention of nuisance shutdowns and “blackouts” 
- Rejection-style design prevents replacement errors 
- High-visibility orange label gives instant brand recognition 
- Reduced inventory because A4BQ can replace all older types of Class L fuses now in-service 
- Metal-embossed date and catalog number for traceability and lasting identification 
- Fiberglass body provides dimensional stability in harsh industrial settings 
- High-grade silica filler ensures fast arc quenching 
- Optional mechanical TA indicator (100-6000A). Please contact factory for special trigger actuator 
Applications
- Mains 
- Feeders 
- Large motors 
- Lighting, heating & general loads 
- Circuit breaker back-up 
- DC rated: UPS DC links, battery disconnects, other DC applications 
| Frequency (Hz) | 50/60 Hz | 
| Amperage Range | 100 to 600 A | 
| Fuse Class | Class L | 
| Speed/Characteristic | Time Delay | 
| UL Category Code | JDDZ | 
| CSA File Number | Class 1422-02 Guide 012636_0 | 
| Reach Compliant | Yes | 
| Max Operating Temp. | 80 °C | 
| Max Storage Temp. | 80 °C | 
| Min Storage Temp. | -25 °C | 
| Harmonized System | 853610 | 
| UL File Number | File E2137 | 
Reference Finder
Scroll
| Item number | Ampere rating | Fuse size | Clearing I2t At Rated Voltage | Indication System | Product weight | 
|---|---|---|---|---|---|
| A4BQ400 See product | 400A | - | - | No | 1.1068kg | 
| A4BQ400-TA See product | 400A | - | - | Yes | 1.2701kg | 
| A4BQ4000 See product | 4000A | - | - | No | 1.134kg | 
| A4BQ4000-TA See product | 4000A | - | - | Yes | 11.6573kg | 
| A4BQ450 See product | 450A | - | - | No | 1.1068kg | 
| A4BQ450-TA See product | 450A | - | - | Yes | 1.2701kg | 
| A4BQ500 See product | 500A | - | - | No | 1.1068kg | 
| A4BQ500-TA See product | 500A | - | - | Yes | 1.2701kg | 
| A4BQ5000 See product | 5000A | - | - | No | 14.2882kg | 
| A4BQ5000-TA See product | 5000A | - | - | Yes | 14.3789kg | 
 
  