W1058272 - 4.370.000
NH fuse-switch disconnector MULTIVERT® Size 3 630A 1x4-pole switching Bus bar system 185mm V-terminal
MULTIVERT® NH 4P is the first vertical 4-pole switchable (3P + N) in-line fuse switch disconnector for busbar systems 185mm with an overall width of 100mm. It is the most inovative and cost-efficient market solution to realize grid disconnection on all poles. MULTIVERT® 630A 4P is designed for NH fuse-links in accordance with IEC/EN 60269-2, VDE 0636-2, size 3: 630A. The system is easy to install via bus bar mounting and is short-circuit proof.
NH fuse-switch disconnector MULTIVERT® Size 3 630A 1x4-pole switching Bus bar system 185mm V-terminal
MULTIVERT® NH 4P is the first vertical 4-pole switchable (3P + N) in-line fuse switch disconnector for busbar systems 185mm with an overall width of 100mm. It is the most inovative and cost-efficient market solution to realize grid disconnection on all poles. MULTIVERT® 630A 4P is designed for NH fuse-links in accordance with IEC/EN 60269-2, VDE 0636-2, size 3: 630A. The system is easy to install via bus bar mounting and is short-circuit proof.
Datasheets
Compliances
pdf - 3.13 MB
pdf - 287.07 KB
| Item number | W1058272 | 
| Catalogue No | 4.370.000 | 
| Description | NH fuse-switch disconnector MULTIVERT® Size 3 630A 1x4-pole switching Bus bar system 185mm V-terminal | 
| EAN/UPC Code | 9008567014103 | 
| Frequency (Hz) | 50 ... 60 Hz | 
| Rated voltage AC IEC | 690 V | 
| Ampere Rating | 630 A | 
| Utilization Category | AC 23 B @ Ue = AC 400 V; Ie = 630 A AC 22 B @ Ue = AC 500 V; Ie = 630 A AC 21 B @ Ue = AC 690 V; Ie = 630 A | 
| Switchability | 1x4-pole switching | 
| ROHS Compliant | Yes | 
| AC or DC | AC | 
| Short Circuit Current Rating (SCCR) | 80kA@Ue = AC 400 V; Ie = 630 A / 80kA@Ue = AC 500 V; Ie = 630 A / 50kA@Ue = AC 690 V; Ie = 500 A | 
| Fuse Size | 3 | 
| Design Details | 4P (3P+N) | 
| Number of Poles | 3-Pole+N | 
| Degree of Pollution | 3 | 
| Rated Impulse Withstand Voltage | 8 kV | 
| Rated Insulation Voltage | 1000 V | 
| Rated SC Withstand | 12 kA / 1 s | 
| Max Power dissipation of Fuse Links Pn | 48 W | 
| Max Power dissipation of Solid Links Pn | 17 W | 
| Power Dissipation by Ith without Fuse-Links | 147 W | 
| Power Dissipation by Ith without Solid Links | 243 W | 
| Rated short circuit making capacity with solid links Icm | 16 kA | 
| Installation Mounting | Bus bar system 185 mm | 
| Product Width | 100 mm | 
| Product Length | 186 mm | 
| Product Height | 885 mm | 
| Sell Pack Quantity | 1 EA | 
| Sell Pack Weight | 8.9 kg | 
| Sell Pack Width | 100 mm | 
| Sell Pack Length | 688 mm | 
| Sell Pack Height | 195 mm | 
| Product group | IEC Fuse Switch Disconnectors | 
| Product Weight | 8.9 kg | 
| Conventional Free Air thermal Current With Fuse-Links Ith | 630 A | 
| Conventional Free Air thermal Current - Solid Links | 800 A | 
 
   
   
  