A1023132 - 1.000.903
NH fuse-switch disconnector MULTIVERT® Size 00 160A 1x3-Pole switching Bus bar system 100mm V-terminal
MULTIVERT® NH vertical fuse switch disconnectors meet all functions of NH fuse switch disconnectors. They are designed for installation on to bus bars in triple pole arrangements. MULTIVERT® 160A triple pole switching are for installation on to 100 mm and 185 mm bus bar systems. MULTIVERT® 160A are designed for NH fuse-links in accordance with IEC/EN 60269-2, VDE 0636-2, size 00: 160A. The system is a modular system, that allows the installation of individual components. MULTIVERT® offer the user the possibility of fast and easy installation as well as a high degree of protection during installation and maintenance.
NH fuse-switch disconnector MULTIVERT® Size 00 160A 1x3-Pole switching Bus bar system 100mm V-terminal
MULTIVERT® NH vertical fuse switch disconnectors meet all functions of NH fuse switch disconnectors. They are designed for installation on to bus bars in triple pole arrangements. MULTIVERT® 160A triple pole switching are for installation on to 100 mm and 185 mm bus bar systems. MULTIVERT® 160A are designed for NH fuse-links in accordance with IEC/EN 60269-2, VDE 0636-2, size 00: 160A. The system is a modular system, that allows the installation of individual components. MULTIVERT® offer the user the possibility of fast and easy installation as well as a high degree of protection during installation and maintenance.
Datasheets
Compliances
pdf - 225.55 KB
pdf - 212.49 KB
| Item number | A1023132 | 
| Catalogue No | 1.000.903 | 
| Description | NH fuse-switch disconnector MULTIVERT® Size 00 160A 1x3-Pole switching Bus bar system 100mm V-terminal | 
| EAN/UPC Code | 9008567002803 | 
| Frequency (Hz) | 50 ... 60 Hz | 
| Rated voltage AC IEC | 690 V | 
| Ampere Rating | 160 A | 
| Utilization Category | AC 23 B @ Ue = AC 400 V; Ie = 160 A AC 22 B @ Ue = AC 500 V; Ie = 160 A AC 22 B @ Ue = AC 690 V; Ie = 100 A | 
| Switchability | 1x3-pole switching | 
| ROHS Compliant | Yes | 
| AC or DC | AC | 
| Short Circuit Current Rating (SCCR) | 120kA@Ue = AC 400 V; Ie = 160 A / 120kA@Ue = AC 500 V; Ie = 160 A / 50kA@Ue = AC 690 V; Ie = 100 A | 
| Fuse Size | 00 | 
| Design Details | with cover shroud 1.000.915 | 
| Number of Poles | 3-Pole | 
| Degree of Pollution | 3 | 
| Rated Impulse Withstand Voltage | 8 kV | 
| Rated Insulation Voltage | 1000 V | 
| Rated SC Withstand | 4.5 kA / 1 s | 
| Max Power dissipation of Fuse Links Pn | 12 W | 
| Max Power dissipation of Solid Links Pn | 1.2 W | 
| Power Dissipation by Ith without Fuse-Links | 18 W | 
| Power Dissipation by Ith without Solid Links | 44 W | 
| Rated short circuit making capacity with solid links Icm | 4.5 kA | 
| Installation Mounting | Bus bar system 100 mm | 
| Product Width | 50 mm | 
| Product Length | 116.1 mm | 
| Product Height | 405.9 mm | 
| Sell Pack Quantity | 1 EA | 
| Sell Pack Weight | 1.12 kg | 
| Sell Pack Width | 125 mm | 
| Sell Pack Length | 413 mm | 
| Sell Pack Height | 51 mm | 
| Product group | IEC Fuse Switch Disconnectors | 
| Product Weight | 1.12 kg | 
| Conventional Free Air thermal Current With Fuse-Links Ith | 160 A | 
| Conventional Free Air thermal Current - Solid Links | 250 A | 
 
   
   
   
   
  